Condor Technology

CS Direct Ex Heater

ELECTRICAL DIRECT HEATER – MODEL CS-(*)S (Body: 316 Stainless Steel)

Description

Application

Direct-heaters for Hazardous locations, designed for direct mounting onto e.g. manifolds etc.

  • Anticondensation
  • Freeze protection
  • Temperature maintenance

Features and Advantages

  • Self-limiting heating elements
  • Small dimensions
  • No moving parts, no maintenance required, therefore long lifetime
  • Suitable for T4 and T3 classifications
  • Can be used for 110/240 VAC/DC

Remarks

All Cameo Heaters are designed around self-limiting heating elements. These semi-conductor elements are saving power consumption. Our Cameo Direct-heaters are designed to heat the installed equipment. If properly selected for freeze protection, no thermostat will be needed.

When required in other applications, e.g. analyzers, it is normal practice to use our Direct-heaters in combination with our Fix-Therm96 thermostats (range from 10°C up to 135°C) or our FixTherm Inline Thermostat(range from 10°C up to 60°C).

Range

CS-1S T3 ca. 115°C Surface temperature* 250-25 Watt

CS-2S T4 ca. 105°C Surface temperature* 250-25 Watt

CS-3S T4 ca. 90°C Surface temperature* 250-25 Watt

CS-4S T4 ca. 70°C Surface temperature* 250-25 Watt

* these temperatures are measured at 20 °C ambient temperature.

Technical data

Power 250-25 Watt

Electrical cable 3 x 1 sqmm

Material cable braided silicone, optional: non-braided cable

Standard length ca. 1 mtr. Other lengths optional

Overall dimensions 85x65x28 mm (LxWxH)

Weight ca. 900 g.

Material Stainless steel 316

EX protection class II 2G Ex d IIC T4 or T3

II 2D Ex tD A21 IP66 T 135°C or T200 °C

ATEX Certification KEMA 01ATEX2124X and IECEx DEK 11.0017

IP degree IP 66

Voltage AC/DC 110/240

Ambient temp. range – 60°C….+ 90°C

Datasheet